Timing Verification (IG Mode)

Time Delay Range = 0 to 60,000 ms

Timing Accuracy =

±0.5% or ±½ cycle, whichever is greater + 3 cycles max for currents 1.5 x pickup

Step

Time Delay Setting

Low

Actual Timing

High

Pass/Fail

4

2,000 ms

1,942 ms

2,058 ms

P / F

5

5,000 ms

4,927 ms

5,073 ms

P / F

5

10,000 ms

9,902 ms

10,098 ms

P / F