Timing verification (ig mode, sef) – Basler Electric BE1-11t User Manual

Page 405

Advertising
background image

9424200995 Rev H

393

4

5.0

I2

0.50 A

1.798 sec

1.988 sec

P / F

4

5.0

I2

2.50 A

0.944 sec

1.044 sec

P / F

4

9.9

I2

0.20 A

8.300 sec

9.173 sec

P / F

4

9.9

I2

0.50 A

3.535 sec

3.907 sec

P / F

4

9.9

I2

2.50 A

1.844 sec

2.038 sec

P / F

Timing Verification (IG Mode, SEF)

Time Dial Range = 0.0 to 9.9

Timing Accuracy =

±5% or ±1½ cycles, whichever is greater

Step

Time Dial

Time Curve

Applied Current

Low

Actual Timing

High

Pass/Fail

4

0.5

I2

0.20 A

0.444 sec

0.491 sec

P / F

4

0.5

I2

0.50 A

0.190 sec

0.240 sec

P / F

4

0.5

I2

0.80 A

0.149 sec

0.197 sec

P / F

4

5.0

I2

0.20 A

4.204 sec

4.647 sec

P / F

4

5.0

I2

0.50 A

1.798 sec

1.988 sec

P / F

4

5.0

I2

0.80 A

1.401 sec

1.548 sec

P / F

4

9.9

I2

0.20 A

8.300 sec

9.173 sec

P / F

4

9.9

I2

0.50 A

3.535 sec

3.907 sec

P / F

4

9.9

I2

0.80 A

2.674 sec

3.111 sec

P / F

BE1-11t