Element blocking, Logic connections, Operational settings – Basler Electric BE1-11t User Manual

Page 204

Advertising
background image

192

9424200995 Rev H

Alarms metering screen in BESTCOMSPlus. Refer to the

Alarms

chapter for information on how to

program alarms.

The alarm count can be preset and reset through the front-panel interface or BESTCOMSPlus.

Element Blocking

This input allows for logic supervision or control of the element.

The transformer monitor element has a Block logic input which when true, disables the element by forcing
the element Trip and Pickup outputs to logic 0 and resetting the element timer. An element Block input is
connected to the desired logic in BESTlogicPlus.

Logic Connections

Transformer monitor element logic connections are made on the BESTlogicPlus screen in
BESTCOMSPlus. The transformer monitor element logic block is illustrated in Figure 144. Logic inputs
and outputs are summarized in Table 75.

Figure 144. Transformer Monitor Element Logic Block

Table 75. Logic Inputs and Outputs

Name

Logic Function

Purpose

Block

Input

Disables the 51TF function when true

Trip

Output

True when the 51TF is in a trip condition

Pickup

Output

True when the 51TF is in a pickup condition

Operational Settings

Transformer monitor element operational settings are configured on the Transformer Monitor (51TF)
settings screen (Figure 145) in BESTCOMSPlus. Setting ranges and defaults are summarized in Table
76.

Table 76. Transformer Monitor (51TF) Settings

Setting

Range

Increment

Unit of Measure

Default

Mode

Enabled or Disabled

n/a

n/a

Disabled

Source

CT Circuit 1 or CT Circuit 2

n/a

n/a

CT Circuit 1

Base Current

0 or 0.5 to 16 (5A CT)

0 or 0.1 to 3.2 (1A CT)

0.001

amps

0

Alarm Count

0 or 1 to 99

1

units

1

Threshold

0 or 1 to 40

0.01

units

2

N Constant

0.5 to 3

0.01

units

2

K Constant

1 to 3,000

0.01

units

1,250

Transformer Monitor (51TF)

BE1-11t