520

9424200995 Rev H

Maximum Lead Length ............... 150 feet (4.25 km) with 22 AWG (0.326 mm

2

) wire

Sensing Current Level ................ 2.5 mA
Isolation ...................................... 35 Vpp

Analog Outputs

The RTD module contains four programmable analog outputs.
Rating ......................................... 4 to 20 mAdc or 0 to 10 Vdc (user-selectable)

Current

Accuracy.....................................

±0.053% of full scale (10 V) at 25°C

Temperature Dependence .........

±0.029% drift per degree Celsius

Voltage

Accuracy.....................................

±0.055% of full scale (20 mA) at 25°C

Temperature Dependence .........

±0.04% drift per degree Celsius

Alarm Contact

Type ........................................... Form C (SPDT)
Rating ......................................... 24/48/125/250 Vdc at:

o

30 A make for 0.2 seconds

o

7 A continuous

o

0.3 Adc Break (L/R = 0.04)

Communication Interface

Ethernet

An RTD module with part number 9444100101 is equipped with both fiber and copper Ethernet
connections. An RTD module with part number 9444100100 is equipped with only a copper Ethernet
connection.

Copper Type (RJ45 Connector)

Version ...................................................................... 10BASE-T/100BASE-TX
Maximum Length (One Network Segment) ............... 328 ft (100 m)

Fiber Optic Type (ST Connector)

Version ...................................................................... 100BASE-FX, multimode
Maximum Length (Half-Duplex) ................................ 1,310 ft (399 m)
Maximum Length (Full-Duplex) ................................. 6,600 ft (2,011 m)

Serial

RS-485 19,200 baud

Temperature

Operating Range ........................ –40

°C to 70°C (–40°F to 158°F)

Storage Range ........................... –40

°C to 70°C (–40°F to 158°F)

Standards

IEC 60068-1:

Environmental Testing Part 1: General and Guidance. Temperature Test

IEC 60068-2-1: Basic Environmental Testing Procedures, Part 2: Tests - Test Ad: Cold (Type Test)

IEC 60068-2-2: Basic Environmental Testing Procedures, Part 2: Tests - Test Bd: Dry Heat (Type Test)

IEC 60068-2-28: Environmental Testing Part 2: Testing-Guidance for Damp Heat Tests

IEC 60068-2-38: Composite Temperature/Humidity Cyclic Test

IEC 60255-4:

Single Input Energizing Quantity Measuring Relays with Dependent Specified Time

RTD Module