9424200995 Rev H

221

Figure 175. BE1-11t Connected for Primary Protection, BE1-851 Connected for Independent Backup

Notes for Figure 175:

1.

With the appropriate transformer and CT connection information, the BE1-11t can automatically
determine the required compensation. The BE1-11t can accommodate any combination of
transformer and CT connection (wye, delta AB, or Delta AC). For more information, refer to the

Configuration

chapter.

2.

Independent ground input (I

G

) can be connected for overcurrent or neutral differential protection.

3.

Phase, residual, and I

2

overcurrent elements can be connected to any CT circuit for backup

protection.

4.

Overcurrent neutral ground (I

N

) operates on internally calculated residual (3I0) current.

5.

A four-wire connection is shown as typical. For more information on VTP connections, refer to the

Typical Connections

chapter.

6.

The polarity of metered watts and vars can be adjusted using BESTCOMSPlus.

7.

Shown with separate, overlapping CT for independent backup protection.

BE1-11t

Power System Applications