N table 52 – Basler Electric BE1-11t User Manual

Page 144

Advertising
background image

132

9424200995 Rev H

Figure 93. Setting Group Setup Screen

Table 52. Operational Settings

Setting

Range

Purpose

Default

Mode

Disabled
Discrete Inputs
Binary Inputs

Sets the mode of the setting group selection function.
(If Auto mode is desired, logic mode must be either 1 or
2.)

Disabled

Source

CT Circuit 1 or CT
Circuit 2

n/a

n/a

Switch

Threshold

0 to 25A (5A CTs)
0 to 5A (1A CTs)

Measured current of the SG0 Monitor Setting that must
be exceeded for a setting group change to occur. (Set in
increments of 0.01A)

0

Switch

Time

0 = Disabled
1 to 60 minutes

Time, in minutes, that determines when a setting change
occurs once the Switch Threshold setting is exceeded.

0

Return

Threshold

0 to 25A (5A CTs)
0 to 5A (1A CTs)

Measured current of the SG0 Monitor Setting that the
monitored current must decrease below in order for a
return to SG0. (Set in increments of 0.01A)

0

Return

Time

0 = Disabled
1 to 60 minutes

Time, in minutes, that determines when a return to SG0
will occur once the monitored current has decreased
below the Return Threshold setting.

0

Setting Groups

BE1-11t