Inverse time verification – Basler Electric BE1-11t User Manual

Page 331

Advertising
background image

9424200995 Rev H

319

Step 10: (Optional.) Repeat steps 1 through 9 for the B-phase and C-phase voltage inputs.

Step 11: (Optional.) Repeat steps 1 through 10 for settings group 1, 2, and 3.

Step 12: Use BESTCOMSPlus to open the Protection, Voltage, Overexcitation (24) screen and send the

test settings in Table 107 to the BE1-11t.

Table 107. Definite Time Pickup Test Settings

Setting

Value

Description

Inverse Time Pickup

0

Disables Inverse Time Pickup

Definite Timer 1 Pickup

2.36

Sets Definite Timer 1 Pickup at 118% of nominal (2.36 V/Hz)

Definite Timer 1 Time Delay

50

Sets Definite Timer 1 Time Delay at 50 ms (minimum)

Definite Timer 2 Pickup

0

Disables Definite Timer 2 Pickup

Alarm Pickup

0

Disables Alarm Pickup

Step 13: Prepare to monitor the operation of the Definite Timer 1 Pickup. Pickup operation can be

verified by monitoring OUT2. Operation of the Definite Timer 1 Trip can be verified by
monitoring OUT1.

Step 14: Connect a three-phase, 100 Vac/50-Hz or 120 Vac/60-hertz voltage source (depending on

user's nominal frequency) to Terminals C13 (A-phase), C14 (B-phase), C15 (C-phase), and
C16 (neutral).

Step 15: Apply A-phase voltage at nominal frequency and slowly increase until OUT2 closes (V/H Trip x

Freq = PU) and record the pickup. Verify that there is a 24 target on the front-panel display.
Slowly decrease the A-phase voltage until OUT2 opens and record the dropout.

Step 16: (Optional.) Repeat steps 12 through 15 for higher and lower pickup settings.

Step 17: (Optional.) Repeat steps 12 through 16 for frequencies other than nominal.

Step 18: (Optional.) Repeat steps 12 through 17 for the B-phase and C-phase voltage inputs.

Step 19: (Optional.) Repeat steps 12 through 18 for settings group 1, 2, and 3.

Step 20: (Optional.) Set Definite Timer 1 Pickup to 0 and Definite Timer 2 Pickup to 2.36 V/Hz and repeat

steps 12 through 19 for Definite Timer 2 Pickup.

Inverse Time Verification

The following test uses the (M-1)^2 time curve.

Step 1: Use BESTCOMSPlus to open the Protection, Voltage, Overexcitation (24) screen and send the

test settings in Table 108 to the BE1-11t.

Table 108. Inverse Time Verification Test Settings

Setting

Value

Description

Inverse Time Pickup

2.1

Sets Inverse Time Pickup at 1.05% of nominal (2.10 V/Hz)

Inverse Time Dial

0.5

Sets Inverse Time Dial at 0.5

Inverse Reset Dial

0

Sets Inverse Reset Dial at minimum

Curve Exponent

2

Sets Curve Exponent to 2

Definite Timer 1 Pickup

0

Disables Definite Timer 1 Pickup

Definite Timer 2 Pickup

0

Disables Definite Timer 2 Pickup

Alarm Pickup

0

Disables Alarm Pickup

Step 2: Connect and apply 120 Vac, three-phase, 60-hertz voltage source to Terminals C13 (A-phase),

C14 (B-phase), C15 (C-phase), and C16 (neutral).

BE1-11t

Overexcitation (24) Test