Functional test report, Overfrequency pickup verification – Basler Electric BE1-11t User Manual

Page 372

Advertising
background image

360

9424200995 Rev H

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 253.

Blocking is disabled.

OUT1 closes for 81-1 Trip.

OUT2 closes for 81-1 Pickup.

Fault recording is enabled.

Figure 253. BESTlogicPlus Settings (ROC Inhibit)

Step 3: To test the negative-sequence inhibit, connect a three-phase voltage source with 120 degrees

between phases. The negative-sequence quantity is based on phase to neutral nominal voltage
(69.3 or 120). The negative-sequence inhibit setting is a percent of nominal voltage. Assuming a
4-wire connection and a nominal voltage of 120 volts phase-to-neutral, 208 phase-to-phase, a
20% of nominal setting equates to a negative-sequence voltage of 24 volts.

Step 4: Set the rate of change (sweep or ramp) for 3 Hz/s (BE1-11t set to trip at 2 Hz/sec), initiate the

sweep, and note that OUT2 operates. While monitoring Metering of the BE1-11t, reduce the C-
phase voltage to 55 volts and note the negative-sequence voltage. Continue to reduce the C-
phase voltage in 1-volt increments repeating the sweep test after each reduction until OUT2
does not operate. Inhibit should occur at 24 volts negative-sequence. Record the result.

Step 5: Set the Negative Sequence Inhibit setting to 0%.

Step 6: To test the frequency limit inhibit function, connect a 120 Vac voltage source capable of

smoothly sweeping the frequency from 35 Hz to 75 Hz to terminals C13 (A-phase) and C16
(neutral). With a ROC setting of 2 Hz/sec, initiate a 3 Hz/sec sweep (frequency range set 60 Hz
to 57 Hz) and note that OUT2 operates.

Step 7: Set the Overfrequency Inhibit setting to 59.7 Hz and the Underfrequency Inhibit setting to 59.5

Hz. Repeat step 6 and note that OUT2 does not operate. Pickup accuracy for over and
underfrequency limit is

±0.01 Hz.

Functional Test Report

Overfrequency Pickup Verification

Pickup Setting Range = 15 to 70 Hz

Pickup Accuracy =

±0.01 Hz

Dropout = 0.02 Hz

±0.01 Hz of the actual pickup value

Step

Pickup

Setting

Low

Actual

Pickup

High

Low

*

Actual

Dropout

High

*

Pass/Fail

6

65 Hz

64.99 Hz

65.01 Hz

64.97 Hz

64.99 Hz

P / F

7

67 Hz

66.99 Hz

67.01 Hz

66.97 Hz

66.99 Hz

P / F

7

69 Hz

68.99 Hz

69.01 Hz

68.97 Hz

68.99 Hz

P / F

* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.

Frequency (81) Test