521

IEC 60255-5:

Electrical Insulation Tests for Electrical Relays. Dielectric Test and Impulse Test

IEC 60255-6:

Electrical Relays - Measuring Relays and Protection Equipment

IEC 60255-21-1: Vibration, Shock, Bump, and Seismic Tests on Measuring Relays and Protective

Equipment (Section 1 - Vibration Test - Sinusoidal). Class 1

IEC 60255-21-2: Vibration, Shock, Bump, and Seismic Tests on Measuring Relays and Protective

Equipment (Section 2 - Shock and Bump Test - Sinusoidal). Class 1

IEEE C37.90.1: Surge Withstand Capability (SWC) Tests for Relays and Relay Systems Associated

with Electric Power Apparatus

IEEE C37.90.2: Withstand Capability of Relay Systems to Radiated Electromagnetic Interference from

Transceivers

UL Approval

“cURus” recognized to UL Standard 508 & CSA Standard C22.2 No.14

“cURus” recognized per Standard ISA 12.12.01, Electrical Equipment for Use in Class I and II, Division
2, and Class III Division 1 and 2 Hazardous (Classified) Locations.
For use in Class I, Division 2,
Groups A, B, C, D, Temperature Code - T4 & CSA C22.2 No. 213-M1987 (Reaffirmed 1999). For use in
Class I, Division 2 Hazardous locations.

CSA Certification

CSA certified to Standard C22.2 No.14.

CE Compliance

This product meets or exceeds the standards required for distribution in the European Community.

This product complies with the requirements of the following EC Directives:

Low Voltage Directive (LVD) - 73/23/EEC as amended by 93/68/EEC

Electromagnetic Compatibility (EMC) - 89/336/EEC as amended by 92/31/EEC and 93/68/EEC

This product conforms to the following Harmonized Standards:

EN 50178:1997 - Electronic Equipment for use in Power Installations

EN 61000-6-4:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Emission
Standard for Industrial Environments

EN 61000-6-2:2001 - Electromagnetic Compatibility (EMC), Generic Standards, Immunity for
Industrial Environments

EN 61000-4-2: Electrostatic Discharge Immunity

EN 61000-4-3: Radiated, Radio-Frequency, Electromagnetic Field Immunity

EN 61000-4-4: EFT Immunity

EN 61000-4-5: Surge Immunity

EN 61000-4-6: Conducted Immunity

EN 61000-4-8: Power Frequency Magnetic Field Immunity

EN 61000-4-11: Voltage Dips and Interrupts

HALT (Highly Accelerated Life Testing)

Basler Electric uses HALT to prove that our products will provide the user with many years of reliable
service. HALT subjects the device to extremes in temperature, shock, and vibration to simulate years of
operation, but in a much shorter period span. HALT allows Basler Electric to evaluate all possible design
elements that will add to the life of this device. As an example of some of the extreme testing conditions,
the RTD module was subjected to temperature extremes of

–80°C to +130°C,

vibration extremes of 5 to

45 G at +20

°C, and temperature/vibration extremes of 45 G over a temperature range of –60°C to

+110

°C. Combined temperature and vibration testing at these extremes proves that the RTD module is