Under/Overvoltage (27/59)

The 27 and 59 elements have independent user defined definite and inverse time delays. The inverse
time curves are defined below.

Undervoltage (27) Inverse Time Curve

The undervoltage inverse time curve is defined by Equation 33 and shown in Figure 304.

𝑇

𝑇

=

𝐷

1 − �𝑉

𝑚

𝑉

𝑝𝑢

Equation 33. Undervoltage (27) Inverse Time Curve Definition


where:

T

T

= Time to Trip

D

= Time Dial

V

m

= Measured Voltage

V

pu

= Voltage Pickup Setting

BE1-11t

Time Curve Characteristics