81 - frequency protection, 87 - phase current differential protection – Basler Electric BE1-11t User Manual

Page 461

Advertising
background image

9424200995 Rev H

449

Zero Sequence Polarization (V)

VOIN - Calculated Zero Sequence Voltage compared to Calculated Zero Sequence Current.

VOIG - Calculated Zero Sequence Voltage compared to Measured Ground Current.

VXIN - Measured 3V0-VX Input compared to Calculated Zero Sequence Current.

VXIG - Measured 3V0-VX Input compared to Measured Ground Current.

81 - Frequency Protection

O/U

Pickup

Setting Range ........................................................... 15 to 70 Hz
Accuracy....................................................................

±0.01 Hz

Dropout ...................................................................... 0.02 Hz

±0.01 Hz of the actual pickup value

Time Delay

Setting Range ........................................................... 0 to 600,000 ms
Accuracy....................................................................

±0.5% or ±1 cycle, whichever is greater, plus 3

cycle recognition time for time delays < 50 ms

ROC

Pickup

Setting Range ........................................................... 0.2 to 20 Hz/sec (positive, negative, or either)
Accuracy....................................................................

±2% or ±0.1 Hz/sec of the setting, whichever is

greater

Dropout ......................................................................

±3% of the actual pickup value

Over/Underfrequency Inhibit

Setting Range ........................................................... 15 to 70 Hz
Increment .................................................................. 0.01 Hz
Accuracy....................................................................

±0.01 Hz

Negative-Sequence Inhibit

Setting Range ........................................................... 0 to 99% of nominal voltage
Accuracy....................................................................

±0.5% or ±1 V, whichever is greater

Time Delay

Setting Range ........................................................... 0 to 600,000 ms
Accuracy....................................................................

±0.5% or ±1 cycle, whichever is greater, plus

recognition time

*

* Recognition time = 2 cycles for 0.57 > pickup, 4 cycles for 0.24 > pickup, 8 cycles for 0.08 > pickup, 16
cycles at pickup

O/U/ROC Voltage Inhibit
Setting Range ........................................................... 15 to 250 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

87 - Phase Current Differential Protection

Restrained Differential
5 Ampere CT Pickup Accuracy .................................

±4% or ±75 mA, whichever is greater

1 Ampere CT Pickup Accuracy .................................

±4% or ±25 mA, whichever is greater

Response Time ......................................................... <2 cycles at 5 times pickup

<3 cycles at 1.5 times pickup

TAP
5 Ampere CT Setting Range ..................................... 2.00 to 20.0 A
1 Ampere CT Setting Range ..................................... 0.40 to 4.00 A