Setting

Value

BESTCOMSPlus Screen

Description

Element Mode

IA

Protection, Current,
Instantaneous Overcurrent (50-1)

Enables 50-1 function for
IA mode

Direction

Forward Protection, Current,

Instantaneous Overcurrent (50-1)

Selects forward direction
for 50-1

Element Mode

3I0

Protection, Current,
Instantaneous Overcurrent (50-2)

Enables 50-2 function for
3I0 mode

Direction

Forward Protection, Current,

Instantaneous Overcurrent (50-2)

Selects forward direction
for 50-2

Element Mode

I2

Protection, Current,
Instantaneous Overcurrent (50-3)

Enables 50-3 function for
I2 mode

Direction

Forward Protection, Current,

Instantaneous Overcurrent (50-3)

Selects forward direction
for 50-3

50-1 67 A

Enabled Target Configuration, Targets

Enables phase A
directional target for 50-1

50-2 67 Residual

Enabled Target Configuration, Targets

Enables residual
directional target for 50-2

50-3 67 Neg SEQ

Enabled Target Configuration, Targets

Enables Neg SEQ
directional target for 50-3

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 264.

Blocking is disabled.

OUT1 closes for 50-1 Trip.

OUT2 closes for 50-2 Trip

OUT3 closes for 30-3 Trip.

Fault recording is enabled for 50-1, 50-2, and 50-3.

Figure 264. BESTlogicPlus Settings

Directional Overcurrent (67) Test