IRIG Verification (if used)

Purpose: To verify that the BE1-11t acquires and updates IRIG time and date information.

Step 1: Connect a suitable IRIG source to BE1-11t terminals A1 (+) and A2 (

–).

Step 2: Upon receiving the IRIG signal, the BE1-11t clock will be updated with the current time, day,

and month. Verify this on the Metering > Status > Real Time Clock screen on the front-panel
display.

Contact Sensing Inputs

Purpose: To verify that the BE1-11t senses hardware input status.

Step 1: Apply an external voltage source within the range of the voltages listed in Table 101 to contact

sensing inputs IN1 (B1/B2), IN2 (B3/B4), IN3 (B5/B6), IN4 (B7/B8), IN5 (E1/E2), IN6 (E3/E4),
and IN7 (E5/E6).

Table 101. Contact Sensing Turn-On Voltages

Style Option

Nominal Input Voltage

Contact Sensing Turn-On Voltage

*

Jumper Installed

(Low Position)

Jumper Not Installed

(High Position)

Txx1xxxxxxxxxx

48 Vdc or 125 Vac/dc

26 to 38 Vdc

69 to 100 Vdc

56 to 97 Vac

Txx2xxxxxxxxxx

125/250 Vac/dc

69 to 100 Vdc

56 to 97 Vac

138 to 200 Vdc
112 to 194 Vac

Txx3xxxxxxxxxx

24 Vdc

n/a

Approx. 5 Vdc

* For information on setting contact-sensing input jumpers, refer to the

Contact Inputs and Outputs

chapter.

Step 2: To verify that all inputs have been detected, use the Metering Explorer in BESTCOMSPlus to

open the Status, Inputs screen.

Control Outputs

Purpose: To verify that the BE1-11t senses hardware output status.

Step 1: Connect to the BE1-11t through BESTCOMSPlus.

Step 2: Use the Metering Explorer to open the Control, Output Override screen.

Step 3: Click on the Disabled button for Output #1. The button changes to Enabled indicating that the

output control override capability of the relay is enabled.

Step 4: Select Set from the Action drop-down menu and click on the green arrow button to energize

Output #1. Verify that the Output #1 Status LED, located on the Output Override screen of
BESTCOMSPlus, turns on. Navigate to Metering > Status > Outputs on the front-panel display
and verify that Output #1 changes state.

Step 5: Select Reset from the Action drop-down menu and click on the green arrow button to de-

energize Output #1. Verify that the Output #1 Status LED, located on the Output Override
screen of BESTCOMSPlus, turns off. Navigate to Metering > Status > Outputs on the front-
panel display and verify that Output #1 changes state.

Step 6: Verify that the sequence of events recorder logged the events by using the Metering Explorer in

BESTCOMSPlus to open the Reports, Sequence of Events screen.

Acceptance Testing