Pickup verification (ig mode) – Basler Electric BE1-11t User Manual

Page 381

Advertising
background image

9424200995 Rev H

369

Pickup Verification (IG Mode)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 164 to the BE1-11t. Reset all

targets.

Table 164. Operational Settings (IG Mode)

Setting

Value

BESTCOMSPlus Screen

Description

Ground CT
Ratio

1

System Parameters, Sensing
Transformers

Sets ground CT ratio to 1

Element Mode

IG

Protection, Current, Instantaneous
Overcurrent (50-1)

Enables 50-1 function for IG
mode

Source

CT Circuit 1

Protection, Current, Instantaneous
Overcurrent (50-1)

Selects CT circuit 1 as the
source

50-1 IND GND

Enabled

Target Configuration, Targets

Enables IND GND target for
50-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 257.

Blocking is disabled.

OUT1 closes for 50-1 Trip.

OUT2 closes for 50-1 Pickup.

Fault recording is enabled.

Figure 257. BESTlogicPlus Settings (IG Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Current, Instantaneous Overcurrent (50-1) screen

and send the low range test settings (minimum pickup setting) to the BE1-11t for your sensing
input type in Table 165.

Table 165. Pickup Test Settings (IG Mode)

Sensing Input Type

Range

Pickup Setting

Time Delay

5 A

Low

0.5 A

0 ms

Middle

5.0 A

0 ms

High

10.0 A

0 ms

1 A or SEF

Low

0.1 A

0 ms

Middle

1.0 A

0 ms

High

2.0 A

0 ms

Step 4: Prepare to monitor the 50-1 function operation. Operation can be verified by monitoring OUT2

(see Figure 257).

Step 5: Connect a current source to terminals D7 and D8 (IG).

BE1-11t

Instantaneous Overcurrent (50) Test