Energy data reporting, 24 - overexcitation protection, 27p - phase undervoltage protection – Basler Electric BE1-11t User Manual

Page 456

Advertising
background image

444

9424200995 Rev H

Reactive Power
5 Ampere CT Range ................................................. –7,500 var to +7,500 var
1 Ampere CT Range ................................................. –1,500 var to +1,500 var
Accuracy....................................................................

±1% at zero power factor

Energy Data Reporting

5 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
1 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
Units of Measure ....................................................... kilo
Rollover Value of Registers....................................... 1,000,000,000 kWhr or kvarhr
Accuracy....................................................................

±1% at unity power factor

24 - Overexcitation Protection

Inverse Time
Curve Exponent ........................................................ 0.5, 1, or 2

Pickup

Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy....................................................................

±2% or ±0.05 V/Hz, whichever is greater

Dropout/Pickup Ratio ................................................ 98%

±1%

Time Dial

Setting Range ........................................................... 0.0 to 9.9
Accuracy....................................................................

±5% or ±3 cycles, whichever is greater

Reset Dial

Setting Range ........................................................... 0.0 to 9.9
Accuracy....................................................................

±5% or ±3 cycles, whichever is greater

Definite Time 1 and 2

Pickup

Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy....................................................................

±2% or ±0.05 V/Hz, whichever is greater

Time Delay

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±1.5% or ±3 cycles, whichever is greater

Alarm

Pickup

Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy....................................................................

±2% or ±0.05 V/Hz, whichever is greater

Reset/Alarm Ratio ..................................................... 98%

±1%

Time Delay

Setting Range ........................................................... 50 to 600,000 ms
Accuracy....................................................................

±0.5% or ±3 cycles, whichever is greater

27P - Phase Undervoltage Protection

Pickup
Setting Range ........................................................... 1 to 300 V
Accuracy....................................................................

±2% or ±1 V, whichever is greater

Reset/Pickup Ratio .................................................... 102%

±1%

Specifications

BE1-11t