Pickup verification (v1 mode) – Basler Electric BE1-11t User Manual

Page 357

Advertising
background image

9424200995 Rev H

345

Step 2: Prepare to monitor the 59X-1 timings. Timing accuracy is verified by measuring the elapsed

time between a sensing voltage change and OUT1 closing.

Step 3: Connect and apply a 150 Vac, three-phase voltage source to terminals C13 (A-phase), C14 (B-

phase), C15 (C-phase), and C16 (neutral).

Step 4: Step the A-phase voltage up to 215 volts. Measure the time delay and record the result.

Step 5: Repeat step 4 for the 5,000 ms and 10,000 ms time delay settings of Table 135. Record the

results.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 59X-2, 59X-3, and 59X-4.

Pickup Verification (V1 Mode)

Step 1: Use BESTCOMSPlus to send the operational settings in Table 136 to the BE1-11t. Reset all

targets.

Table 136. Operational Settings (V1 Mode)

Setting

Value

BESTCOMSPlus Screen

Description

Phase VT Ratio

1

System Parameters, Sensing
Transformers

Sets phase VT ratio to 1

Phase VT
Connection

4W-Y

System Parameters, Sensing
Transformers

Sets phase VT connection to
4W-Y

27/59 Mode

PN

System Parameters, Sensing
Transformers

Sets 27/59 mode to phase-
neutral

Element Mode

V1

Protection, Voltage, Overvoltage
(59X-1)

Enables 59X-1 function for V1
mode

Timing Mode

Definite

Protection, Voltage, Overvoltage
(59X-1)

Selects definite timings

59X-1 V1

Enabled Target Configuration, Targets

Enables V1 target for 59X-1

Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 246.

Blocking is disabled.

OUT1 closes for 59X-1 Trip.

OUT2 closes for 59X-1 Pickup.

Fault recording is enabled.

Figure 246. BESTlogicPlus Settings (V1 Mode)

Step 3: Use BESTCOMSPlus to open the Protection, Voltage, Overvoltage (59X-1) screen and send

the first row of test settings in Table 137 to the BE1-11t.

BE1-11t

Auxiliary Overvoltage (59X) Test

Advertising