Timing verification (ig mode) – Basler Electric BE1-11t User Manual

Page 399

Advertising
background image

9424200995 Rev H

387

Table 183. Pickup Test Settings (IG Mode)

Sensing Input

Type

Range

Pickup Setting

Time Dial

Time Curve

5 A

Low

0.5 A

0

I2

Middle

5.0 A

0

I2

High

16.0 A

0

I2

1 A

Low

0.1 A

0

I2

Middle

1.0 A

0

I2

High

3.2 A

0

I2

SEF

Low

0.01 A

0

I2

Middle

0.5 A

0

I2

High

0.8 A

0

I2

Step 9: (Optional.) Repeat steps 1 through 8 for 51-2, 51-3, 51-4, 51-5, 51-6, 51-7, 51-8, and 51-9.

Step 10: (Optional.) Repeat steps 1 through 9 with CT Circuit 2 as the source. In step 5, replace D1 with

F1, D2 with F2, etc.

Timing Verification (IG Mode)

Step 1: Use BESTCOMSPlus to open the Protection, Current, Inverse Overcurrent (51-1) screen and

send the test settings in Table 184 to the BE1-11t.

Table 184. Timing Test Settings (IG Mode)

Pickup Setting

Time Curve

0.5 A (5 A sensing), 0.1 A (1 A sensing)

I2

Step 2: Prepare to monitor the 51-1 timings. Timing accuracy is verified by measuring the elapsed time

between a sensing current change and OUT1 closing.

Step 3: Connect a current source to BE1-11t terminals D7 and D8 (IG).

Step 4: Using the values listed in Table 185, apply the appropriate current values, and measure the

time between the application of current and the closure of OUT1. Record the results.

Step 5: Repeat step 4 for all of the current and time dial settings for your current sensing type.

Step 6: (Optional.) Repeat steps 1 through 5 for settings group 1, 2, and 3.

Step 7: (Optional.) Repeat steps 1 through 6 for 51-2, 51-3, 51-4, 51-5, 51-6, 51-7, 51-8, and 51-9.

Step 8: (Optional.) Repeat steps 1 through 7 with CT Circuit 2 as the source. In step 3, replace D1 with

F1, D2 with F2, etc.

BE1-11t

Inverse Overcurrent (51) Test