<I ISA100 device configuration>

I-41

IM 01R01A01-01E

9th Edition : May 31, 2013-00

Change of ISA100 device parameters

Changing the value of parameters requires Block Mode of Function Block of the accessed

ISA100 device to be O/S mode (Out of Service mode) in the most situations.
DTM provides automatic Block Mode change functions as follows.
Function Block to be O/S mode when changing the value of parameters.
Function Block to be recovered when completing the value changes.
Function Block to be O/S mode during download.
The function above is not effective as default. Press “Option button” in the DTM, open Option

window, select “ISA100” in “Change to O/S mode, while download” and press “OK”.

I060203E.ai

Figure I-6-3

Table I-6-1

Item

Object

Description

Default

Change to O/S

mode, while

download

FOUNDATION

fieldbus

Block Mode of Function Block changes to O/S while

downloading to FOUNDATION fieldbus device

automatically.

This is not applicable to ISA100, HART device DTM.

ON

ISA100

Block Mode of Function Block changes to O/S while

downloading to ISA100 device automatically.

This is not applicable to FOUNDATION fieldbus,

HART device DTM.

OFF

Update cycle

Dynamic variable

Specify update cycle of Dynamic variable in the DTM.

5 to 120 sec selectable.

30 sec

Static variable

Specify update cycle of Static variable in the DTM. 60

to 120 sec selectable.

60 sec

Image

Specify update cycle of Image in the DTM. I.e.

Bitmap. 60 to 120 sec selectable.

60 sec

Redirect the access to another ISA100 device.

Close the current DTM Works once. And update in the Segment Viewer and start DTM again.