B-4 Notes on PROFIBUS

PROFIBUS Interface Configuration is required after FieldMate and communication driver

installation. The following initial setup needs to be defined based on the PROFIBUS

communication driver.

1. Start FieldMate and navigate through [Tool] - [PROFIBUS Interface Configuration…].

B040101E.ai

Select the board recognized.

Set a proper baud rate.

Example:

When a PA device is connected via a DP/PA

coupler (Siemens), the baud rate is 45.45 kbit/s.

When a PA device is connected via a DP/PA

coupler (P+F), the baud rate is 93.75 kbit/s.

Figure B-4-1

PROFIBUS Interface Configuration

2. Select [Advanced Setup…] and open the following window. It is advisable to make sure the

following busparameter setting are same as ones of Class 1 Master on PROFIBUS network

to which FieldMate is connected before operation.

B040102E.ai

Figure B-4-2

Advanced Setup