E-3 Device Adjustment/Setting Functions

In this part, basic device communication setting is made and the device parameters are

adjusted and set.
There are three device parameter adjustment/setting functions: DTM Works, Parameter

Manager, and DD Menu.

E-3-1 Basic Device Communication Setting

Tag/Address Assignment

This function assigns device tags and addresses for FOUNDATION fieldbus device.
Address setting of PROFIBUS device is performed in device DTM window. Refer to Part E-3-2,

explanation of Setting Device Station Address for PROFIBUS Devices.
Address of BRAIN device is always “0.”

Startup

Select Segment Viewer – Select Device – Action to activate Tag/Address Assignment.

E030101E.ai

Enter the tag to change.

Select the address to be modified.

The selectable address range is as

shown below:

For HART5: 0 to 15

For HART6, 7: 0 to 63

For FOUNDATION fieldbus H1: 16

to 247

Addresses other than the local

address that have already been

displayed in Segment Viewer are

removed from the objects to be

selected.

These items are indicated only for FOUNDATION

fieldbus H1 devices. If Tag Clear is selected, Address

Clear is also automatically selected.

Figure E-3-1

Tag/Address Assignment