<Appendix I How to clear VCR (NI-FBUS only)>

App.-57

IM 01R01A01-01E

9th Edition : May 31, 2013-00

Operation Procedure

In case that FOUNDATION fieldbus H1 communication suddenly stops, which functioned

properly on FieldMate before, execute the following operation procedure.
1. Exit FieldMate.
2. Activate /FM/Tool/FMNIFBUSClear.exe
3. A window above is displayed. Check “Number of Configured VCRs”. If the values are close

to 100, VCR needs to be cleared. Proceed 3. If the valued are small, the other cause of

trouble such as communication card disorder is expected.

4. Select “Clear Stored VCRs” and exit.
5. Restart FieldMate and check whether FOUNDATION fieldbus H1 communication functions

properly.