B-3-1 notes on ni-fbus, B-18 – Yokogawa FieldMate User Manual
Page 32

<B Packaging and Installation>
B-18
IM 01R01A01-01E
9th Edition : May 31, 2013-00
B-3 Notes on FOUNDATION fieldbus H1
Device Interface
For a FOUNDATION fieldbus H1 device, you can use FBUS from National Instruments or
FFusb from Softing. For details, see G-4 “FOUNDATION fieldbus Interface Selection.”
B-3-1 Notes on NI-FBUS
NI-FBUS is a driver of National Instruments for FOUNDATION fieldbus H1.
For details on installing the NI-FBUS driver, refer to the corresponding manual of National
Instruments. The following are notes on NI-FBUS.
Installing the NI-FBUS Driver
1. Start the PC, log on as a user with administrator privileges, and then install the driver.
2. Restart the PC.
Settings after Installation
1. After the PC restarts, click the Start menu, point to All Programs, National Instruments, and
NI-FBUS, and then select Interface Configuration Utility, or after FieldMate starts, click Tools
and then select FOUNDATION fieldbus Interface Configuration.
2. If a red mark indicating that use is not possible is displayed in the dialog box, select and
right-click on Board0 to choose Enable. This allows the NI-FBUS driver to be enabled.
3. In the dialog box that appears, select Port0 and click the Edit button. Configure the settings
as follows.
Device Address: Visitor
Device Type: Link Master Device
Usage: NI-FBUS
However, for use while connected to a segment under another host, set Device Type to Basic
Device.
NOTE
Connecting the segment under another Host system with Link Master Device, it may cause
communication error.