Table E-3-11
Menu
Description
File
Save Custom TAB Info
Saves the settings in the Custom tab.
Exit
Exits the Parameter Manager.
Edit
Find Parameters
Searches for parameters containing a user-entered character
string from the currently displayed tab.
Undo Modifications
Returns the Work area for the currently displayed tab to its
original state prior to any changes.
View
Show Read Only Parameters
When this item is selected, read-only parameters are also
displayed. It is selected by default. When it is unselected, only
writable parameters are displayed. Read-only parameters are
not displayed.
Tool Bar
When this item is checked, the Show/Hide option for the tool bar
can be selected. It is selected by default (the tool bar is shown).
Result Area
When this item is checked, the Show/Hide option for the
Result area in the lower part of the screen can be selected. It is
selected by default (the Result area is shown).
Status Bar
When this item is checked, the Show/Hide of the status bar can
be selected. It is selected by default (the status bar is shown).
Sorting Order -> By Device Values
Effective when a file has been imported in the Work area.
Displays the parameters in the window in the order they are
defined in the DD. (*1)
Sorting Order -> By Work Area
Effective when a file has been imported in the Work area.
Displays the parameters in the window in the order they are
defined in the file. (*1)
Action Update Device Values – Current TAB (F2)
Reads the parameter values of the currently displayed tab and
updates the Device Values area. The Work area is not updated.
Update Device Values – All TAB (F5)
Performs the above operation for all the tabs.
Update Device Values and Attributes - All TAB
(F1)
Acquires a list of all parameters of the connected device and
their properties, reads all the parameter values, and updates the
Device Values area of all tabs. The Work area is not updated.
Download Checked Parameters - Current
TAB (F3)
Writes parameters in the currently displayed tab that have a
checkmark added to the download checkbox to the device in the
order that they are displayed in the window, and then reads back
only the parameters that were written and updates the Device
Values area.
When the download is successfully completed, any magenta
parameter-value display area in the Work area is returned to its
original color.
Download Checked Parameters - All TAB (F6) Performs the above operation for all the tabs.
Save/Export Device Values
Exports the parameter values (Device Values area) of the actual
device to a file.
Copy Device Values to Work Area
Copies the parameter values (Device Values area) of the
connected device to the Work area.
Load/Import to Work Area
Imports the parameter values from a file and displays them in
the Work area.
Option Change O/S Mode during download
This item is only enabled for FOUNDATION fieldbus H1. When
this item is selected, the Target Mode is set to O/S prior to
downloading and then switched back to the previous mode after
downloading finishes. It is selected by default.
Tool
FOUNDATION fieldbus H1 Block Settings
This item is only enabled for FOUNDATION fieldbus H1. It
enables you to select which function block of an FOUNDATION
fieldbus H1 device to display/set.
Custom Tab Settings
Displays the Custom Tab Settings dialog box.
DD Menu (F7)
Starts the DD Menu. (*2)
*
1:
Effective for FOUNDATION fieldbus only.
*
2:
Starting DD menu, Parameter Manager is minimized.