Appendix C Device Replacement Tool
1. Overview
The device replacement tool simplifies the replacement of Rosemount’s field devices with
Yokogawa’s. This tool converts the parameters of the original device and downloads them to the
replacing device.
This tool can also be used for replacement between Yokogawa’s field devices.
2. Devices
The tool supports the following combinations of Rosemount’s and Yokogawa’s field devices.
Table App.-C-1 Combinations of Field Devices Supported by the Device Replacement Tool
Yokogawa
Replacing device
EJA-A/EJA
HART5
EJA-E
HART5
EJA-E
HART7
EJX
HART5
EJX
HART7
Original device
Rosemount
1151
√
√
√
√
√
2051
√
√
√
√
√
3051C
√
√
√
√
√
3051S
√
√
√
√
√
Yokogawa
EJA-A/EJA
HART5
–
√
√
√
√
EJA-E
HART5
–
–
√
√
√
EJA-E
HART7
–
–
–
–
√
EJX
HART5
–
√
√
–
√
EJX
HART7
–
–
√
–
–
This tool supports HART devices.
The numbers 1151, 2051, 3051C, and 3051S are model names of Rosemount’s pressure
transmitters.
3. Parameters to be converted
The following parameters can be converted:
Tag, Long Tag, LRV, URV, Unit, Pres Damp, Descriptor, Message, Xfer fnctn