9 making the controller ready for operation, Making the controller ready for operation, Commissioning – Lenze 931E/K Small Drives Control User Manual

Page 38: Stop

Advertising
background image

Commissioning

Speed control
Making the controller ready for operation

5

l

38

SW−HB 13.0002−EN 4.1

5.2.9

Making the controller ready for operation

After controller enable, the shaft must start rotating. Unless the motor shows this
behaviour, an error has occurred or the 931E/K servo positioning controller has not been
parameterised correctly. In the below table, you can find typical errors and information on
how to remove them.

Error

Remedy

The motor builds up a holding torque and "snaps" in
different positions.

Pole pair number and/or phase sequence are wrong.
Select the correct pole pair number and/or change the
motor phases. Repeat the automatic identification. See
the chapter "Motor data".

^ 133

The motor shaft vibrates and does not run smoothly.

The selected angle encoder offset and/or controller
parameters are not correct. See the chapter "Speed
control".

^ 34

Repeat the automatic identification. See the chapter
"Angle encoder".

^ 135

The shaft does not rotate.

l

No DC−bus voltage.

l

The limit switches are active.

l

"Quick stop" (DIN 6) has not been assigned correctly.

The shaft does not rotate. The actual value window
displays the speed setpoint = "0".

The speed setpoint has not been configured correctly.
See the chapter "Setpoint selection via setpoint
selectors".

^ 27

(

Stop!

When connecting the motor phases, please observe that the individual servo
motor manufacturers may define different phase sequences. If necessary,
change W and U phase.