Commissioning

Torque control

Setpoint selection via setpoint selectors

5

l

47

SW−HB 13.0002−EN 4.1

Setpoint selection via the analog input

The 931E/K servo positioning controller is equipped with two analog inputs with an input
voltage range of

± 10 V and a resolution of 12 bits. The inputs can be used to enter speed

and torque setpoints.

Select Parameters

W I/Os W Analog inputs or click the "..." button when the analog input

is activated in the setpoint selector menu to open the following menu:

AIN 0

931e_212

Here you can select a "conversion factor" between the input voltage and the Torque or
Speed setpoint.

In the Offset field, you can select a voltage that will be automatically added to the voltage
measured at the analog input. This function may, for instance, be used to compensate for
the offset on the analog control voltage of a control and the offset of the analog input in
the controller. This solves the problem of a very low setpoint still being generated with an
external voltage selection of 0 V.

As another option, you can select positive and negative setpoints with an input voltage of
0 ... 10 V.

The function Safe Zero will limit the detected setpoint to zero, if it is within the voltage
specified in this field. This ensures that the drive will not move or slowly drift away (see the
following figure) with an analog setpoint selection of 0 V.