Commissioning

Torque control

Activating the operating mode

5

l

43

SW−HB 13.0002−EN 4.1

5.3.4

Activating the operating mode

For torque control, configure the command window as follows:

931e_226

The torque setpoint can be selected in A or Nm. Open the menu Options

W Display units to

select the unit. The corresponding menus will then automatically use the selected unit.

If the torque is to be selected in Nm, the torque constant, i.e. the conversion factor between
current and torque, must be known. The torque constant can be entered in the menu
Parameters

W Device parameters W Motor data. Usually, it can also be calculated by means

of the nameplate data on the motor. For this, divide the rated torque by the rated current.

)

Note!

A torque constant of 0 Nm/A is impermissible, if "Torque in Nm" has been
activated.