A2 - 21, Alarm no. : 1099 high temperature – Yaskawa PC NC User Manual

Page 232

Advertising
background image

A2 - 21

YASNAC PCNC Operating Manual Appendix 2: Alarm Tables

2.3 TROUBLESHOOTING

Alarm No. : 1098 Fan is Faulty

ALARM CAUSE

CHECK ITEM

COUNTER MEASURE

Fan is faulty.

Check fan. Ensure connections are

If the fan is faulty, replace it. Contact your

good. Check for obstruction.

Yaskawa representative.

Alarm No. : 1099 High Temperature

ALARM CAUSE

CHECK ITEM

COUNTER MEASURE

Ambient temperature of the NC rack

Open NC door and check that the cooling

If the fan is faulty, replace it. Contact your

exceeded the specified value* due to

fan motor is operating.

Yaskawa representative.

cooling fan failure.

Make sure that air is blowing out through

the ventilation port of the cooling duct.

If cooling fan is block remove obstruction.

* : 70 degC +/- 3 degC

Check to make sure ventilation port of

When measured above CPS-18

cooling duct is not obstructed.

Allow the power supply unit to cool by

Internal temperature of the power supply

turning OFF the power with the NC unit

Change the power supply unit. Contact

unit is high.

door opened. If the alarm occurs even

your Yakawa representative.

after the power supply unit has been

cooled for 30 minutes, the power supply

unit is faulty.

Ambient temperature of the NC unit is high.*

Measure ambient temperature.

This is not the failure of the NC unit.

Remove the cause.

* Allowable temperature range for

If the NC unit is subject to direct sunlight,

‘operation is 0 - 40 degC.

the NC unit temperature will exceed the

allowable limit.