<Indication 1> <Indication 2>

[Discharge abnormality] Compressor's loss of synchronism due to rapid load change, etc.
* Although the outdoor LED indicates abnormality, the compressor restarts and no abnormality

is confirmed.

* This may occur due to the open phase of the compressor or wiring detach.

[F04]

<Indication 1> <Indication 2>

[Discharge temperature sensor (TD) failure]

[F06]

<Indication 1> <Indication 2>

[Heat exchanger temperature sensor (TE) failure]

[F07]

<Indication 1> <Indication 2>

[Heat exchanger temperature sensor (TL) failure]

[F08]

<Indication 1> <Indication 2>

[Outside air temperature sensor (TO) failure]

Check code

Outdoor LED

indication

Check and Action procedure

(No specific description indicates outdoor unit parts.)

TD sensor connector
(CN603) is connected

Correct TD sensor
connection

Replace outdoor control board

No

TD sensor resistance
characteristic is normal

Replace TD sensor

No
See the
characteristic table

on page 101

Yes

Yes

TE sensor connector (CN601)
is connected

Correct TE sensor
connection

Replace outdoor control board

No

Yes

TE sensor resistance
characteristic is normal

Replace TE sensor

No

See the
characteristic table

on page 101

Yes

TL sensor connector (CN604)
is connected

Correct TL sensor
connection

Replace outdoor control board

No

YES

TL sensor resistance
characteristic is normal

Replace TL sensor

No

See the
characteristic table

on page 101

YES

TO sensor connector (CN602)
is connected

Correct TO sensor
connection

Replace outdoor control board

No

Yes

TO sensor resistance
characteristic is normal

Replace TO sensor

No

See the
characteristic table

on page 101

Yes