Operation flow and applicable data, etc.

8-2.

Operation
Mode and
Control Method

The following shows the operation modes and controlled objects.

O Possible

×

Not possible

1) Hot water supply operation
1) Operation start condition

When the [HOT WATER] remote controller button is pressed and
the following operation start condition is met, the operation starts.

• TTW < 38°C is detected.

2) Operation mode determination

An operation mode is determined according to the temperature
of TTW sensor.
• Heat pump operation selection *1 *2
• When TTW < 38°C (a zone in the right figure) is met, the heat

pump operation is selected.

• Heater operation selection

When 45°C TTW < TSC_H (b zone in the right figure) is
met, the heater operation is selected.

• Thermostat status "OFF" selection

When TTW TSC_H is met, the thermostat status "OFF" is
selected.

3) Operation stop

The operation stops in the following cases.
• The remote controller gives a stop instruction.
• TTW TSC_H is met.

*1: When the outside temperature is -20°C or below, the heater

operation is selected even if the TTW temperature falls into "a
zone".

*2: When "Hot water supply" and "Heating" are simultaneously in

operation, the heater operation may be selected depending on
the outside air temperature.

Related FC

*3:When the outside temperature is 0°C or below, the boil-up temperature will be higher that setting temperature in hot

water supply mode.

Operation

mode

Controlled

object

Cooling

only

Heating

only

Hot

water

supply

only

Heating and Hot water

Cooling and Hot water

Heat pump select

for heating

Heat pump select

for hot water

supply

Heat pump select

for cooling

Heat pump select

for hot water

supply

Heating

side

Hot

water

supply

side

Heating

side

Hot

water

supply

side

Cooling

side

Hot

water

supply

side

Cooling

side

Hot

water

supply

side

Heat pump

O

O

O

O

Ч

Ч

O

O

Ч

Ч

O

Backup
heater

×

O

×

O

Ч

Ч

Ч

Ч

Ч

Ч

Ч

Hot water
cylinder
heater

Ч

Ч

O

×

O

×

O

×

O

×

O

(Hot water cylinder unit)

TTW sensor

TTW

HP_H OFF 45°C

HP_H ON 38°C

TSC_H

(Temperature set with

remote controller)

Thermostat OFF c Zone

a Zone

Heater operation

b Zone

Heat pump
operation

TSC_H is hot water temperature
set with remote controller

FC No.

Setting item

Default

Setting available range

1E

Upper limit of hot water supply temperature

75°C

60-80°C

1F

Lower limit of hot water supply temperature

40°C

40-60°C

20

Heat pump start temperature

38°C

20-45°C

21

Heat pump end temperature

45°C

40-50°C

24

Outside air correction start temperature for hot water supply*

3

0°C

-20-10°C

25

Outside air correction temperature for hot water supply*

3

3 deg

0 -15 deg