Toshiba

6

Compressor
Compressor lead

2. Attach the compressor

1) Attach the compressor in the reverse order of the

removal.

Note)

• Be sure to replace the compressor lead after the

compressor replacement. (Compressor lead
spare parts code: 43160591)
At this time, wind the ferrite core with the
compressor lead for 4 times.

• Attach the soundproofing board (Inward

winding, Outward winding), as shown in the right
figure, through between the compressor and
between the piping and parting board.

• Fix the TD sensor with a commercially available

heat resistant binding tie through the piping
cover so that the sensor do not contact the
discharge pipe.

3) Vacuuming

1) Connect the vacuum pump to the charge port and

check joint of the gas piping valve to operate the
vacuum pump.

2) Perform vacuuming until the vacuum low pressure

gauge shows 1(mmHg).

Note)

Open fully the pulse motor valve before
vacuuming. With the valve closed, vacuuming
between the outdoor unit liquid valve and the pulse
motor valve may fail.

How to make pulse motor valve forcible full open
• Turn on the electric leakage breaker.
• Set the SW804 dip switch 1 and 3 on the outdoor

unit control board to ON.

• Press SW801 on the outdoor unit control board

for 1 second or longer.

• After pressing SW801 for 1 second or longer,

turn off the electric leakage breaker within 2
minutes.

4. Charge refrigerant

1) Add refrigerant whose amount is defined

according to the piping length from the valve
charge port. (HWS-1102H, 1402H : 2.7kg)

No.

Exchange parts

name

Work procedure

Remarks

Overlap soundproofing board
(Outward winding) at this position

Place soundproofing board (Outward winding)
through between suction pipe and header pipe

Overlap soundproofing board (Inward winding)
at this position through between compressor,
outlet pipe, and suction pipe

Do not make space between soundproofing boards
(Upper and Outward winding)

Wind ferrite core with
compressor lead
for 4 times

0 to 50
(Compressor lead positioning standard)

Compressor lead

Ferrite core

Suction pipe

Discharge pipe

Soundproofing
board (Upper)

Soundproofing board
(Outward winding)

SW801

SW804

Make the other end of the
line go through under the rivet

Rivet

Header pipe

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 152 Monday, October 5, 2009 2:09 PM