8-2.

Operation
Mode and
Control Method

3) Cooling operation
Pressing the [ZONE1, 2] button and then [OPERATION MODE] starts a cooling operation.

1) Operation start condition

Pressing the [ZONE1, 2] button and then [OPERATION MODE]
starts a cooling operation.

2) Operation mode selection

An operation mode is determined according to the temperature
of TWI sensor.
• Heat pump operation selection *1 *2

When TWI TSC_F (d zone in the right figure) is met, the heat
pump operation is selected.

• Thermostat status "OFF"

When TWI < TSC_F (e zone in the right figure) is met, the
thermostat status "OFF" is selected.

3) Operation stop condition

When either of the following conditions is met, the cooling
operation stops.
• The remote controller gives a stop instruction.
• The operation is switched to heating.

*1: When the outside temperature is 10°C or below, cooling does

not start even if the TWI temperature falls into "d zone".

Related FC

4) Simultaneous operations of "hot water supply" and "heating"

At the time of "Hot water supply" and "Heating" simultaneous
operation, the operation mode is select as follows depending on
the outside air temperature.

• f zone Operation with hot water supply priority

A heat pump operation is performed in the hot water supply side,
and a heating operation in the heating side.

• g zone Operation with heating priority

A heat pump operation is performed in the heating side, and a
heating operation in the hot water supply side.

Operation mode by zone

* Note that after a heat pump operation for "Hot water supply" is selected in f zone, when the operation moves to a

heater operation for "hot water" and then 5 minutes has passed (Hot water supply operation in b zone), the operation
mode changes as follows.

When TTW 45°C (FC: changeable) is met, the operation ends f' zone and returns to f zone.

Related FC

* Note: When user selects “hot water supply” and “ZONE1,2”, and Heat pump selects hot water supply mode, the

Maximum operating time of heat pump is 30 mins.

Item

Operation flow and applicable data, etc.

TWI

TSC_F

(Temperature set with

remote controller)

TSC_F

Thermostat off operation

Heat pump operation
(cooling)

e zone

Diff : 2k

d zone

TSC is a cooling temperature

set with the remote controller

FC No.

Setting item

Default

Setting available range

02

Cooling mode availability

1: No

0: Yes

18

Upper limit of cooling setting temperature

25

18-30°C

19

Lower limit of cooling setting temperature

10

10-18°C

Zone

Hot water supply side

Heating side

f

Heat pump *

Stop *

g

Heater

Heat pump

h

Heater

Heater

D

(Note)

-20

Diff : 5deg

f zone

h zone

Diff : 5deg

g zone

Heater operation

Hot water

supply heat

pump priority

operation

Heating heat

pump priority

operation

TO

Zone

Hot water supply side

Heating side

f'

Heater

Heat pump

FC No.

Setting item

Default

Setting available range

07

Maximum HP operation time in “hot water supply” + “heating
mode”

30 min

0-120min

22

Priority mode switch temperature (D)

0

-20-20°C