9-3. Outline of the determination diagram

The first determination of whether a defective part is in the hydro unit or the outdoor unit can be performed by the
following method.

9-3-1. Procedure of defect diagnosis

In the case of a defect, please apply the following procedure in order to find the defective part.

9-3-2. How to determine from the check code on the remote

control

If the defect is limited by the check code displayed on the remote control, please repair the defect based on the
table on the next page.
The check codes are separated into two groups: software and hardware errors.
Since a hardware error cannot be cancelled without a part replacement etc., please perform a repair.
If its abnormality is determined, the abnormality is noticed by indicating the check code on the remote control check
code display part while letting off a buzzer.

9-3-3. How to cancel a check code on the remote controller

(1) Press

or

button (on the operation side) to clear the check code.

(2) Press

to stop a buzzer for an abnormality only.

Although the above procedure cancels the check code, the hardware error will be displayed again until the
hardware repair is completed.

Defect

Yes

Yes

Yes

No

No

No

Confirm the check
code on the remote
control display

Check code

A01-A12

Check code

L07-L16

Check code

FXX

Defect in Hydro unit

Abnormality in the
communication or setting
system

Abnormality in the water
heat exchange or outdoor
unit sensor system

Abnormality in the outdoor unit or hot-water
tank unit

Check code display part

ZONE1,2

HOT WATER

CL

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 66 Monday, October 5, 2009 2:09 PM