Periodic Inspection Items

For a long-term safe operation of this equipment, perform periodic inspection and parts replacement.

<Inspection items>

Hydro unit

(HWS-802**-E, 1402**-E)

Frequency

Periodic inspection details

1. Insulation measurement (Power source circuit/ Heater

circuit)

Annually

Insulation measurement with a mega tester

2. Power source measurement (No-load voltage)

Annually

Electronic voltage measurement: 230V ±23V

3. Operation check

Annually

Hot water supply/ Heating/ Cooling operation check with
remote controller

4. Refrigerant leakage/ Water leakage inspection

Annually

Visual inspection and check with a leak tester: No leakage
must be found

5. Water heat exchanger inspection (Internal dirt and

clogging)

Annually

Checking for water dirtiness in a closed cycle, Cleaning

6. Inlet/ Outlet water temperature measurement

Annually

Temperature measurement: Temperature measurement
during an operation

7. Circulation pump inspection

Annually

No leakage or abnormal noise must be found (Replacement
every 10 years: Charged)

8. Air vent valve inspection

Annually

Water leakage, Air vent

9. Expansion vessel

Annually

Visual check for charge pressure abnormality, water
leakage, or corrosion

10. Heater assembly

Annually

Check for appearance damage, deformation, or loose
terminal

11. Flow switch

Annually

Operation check while running

12. Manometer

Annually

Water leakage, water pressure check

13. Safety valve

Annually

Water leakage, Appearance check, Drainage check

14. Water heat exchanger control board, Terminal block

Annually

Check for loose connector and connecting terminal

Outdoor unit

(HWS-802H-E, 1102H-E, 1402H-E)

Frequency

Periodic inspection details

1. Insulation measurement (Power source circuit/

Compressor)

Annually

Insulation measurement with a mega tester

2. Power source measurement (No-load voltage/ Rated

operation)

Annually

Electronic voltage measurement: 230V ±23V

3. Operation frequency (Outdoor unit operation check)

Annually

Frequency check by rated operation (See 10-13)

4. Refrigerant leakage inspection

Annually

Visual inspection and check connection with a leak tester:
No leakage must be found

5. Air heat exchanger inspection (Dirt and clogging)

Annually

Visual inspection, Clear clogging

6. Fan inspection (Scratch, damage)

Annually

Check for scratches or damages to the fan or abnormal
motor sound

7. Cycle parts

(Compressor, 4-way valve, Pulse motor valve)

Annually
Annually

Operation check by trial run

8. Inverter control board, Terminal block

Annually

Check for loose connector and connecting terminal

Hot water cylinder

(HWS-150CSHM3-E(-UK),

210CSHM3-E(-UK), 300CSHM3-E(-UK))

Frequency

Periodic inspection details

1. Insulation measurement (Power source circuit)

Annually

Insulation measurement with a mega tester

2. Power source measurement (No-load voltage)

Annually

Electronic voltage measurement: 230V ±23V

3. Water leakage inspection

Annually

Visual inspection for leakage: No leakage must be found

4. Terminal block

Annually

Check for loose connector and connecting terminal

5. Heater assembly

Annually

Check for appearance damage, deformation, or loose
terminal

6. Temperature, Pressure relief valve (Specification for

UK only)

Annually

Drainage check