Toshiba HWS-802XWHT6-E User Manual

Page 118

Advertising
background image

117

Toshiba

12. Forced Defrosting Setting

The FC code setting (See 2-2) can activate the forced defrosting mode for the outdoor unit operation.

(Preparation)

1

Press the remote controller buttons, TEST

, SET

,

and SELECT

, at the same time for 4 seconds

or longer.(Make sure that no operation is in progress.)

2

Specify CODE NO. (FC) 46 with the TEMP.

button for temperature setting.

3

Set DATA to 0001 with the TIME

button for timer

setting. (See display

)

(Factory setting is 0000)

4

Press the SET

button. (If OK

lights, the status is

normal)

5

Pressing the TEST

button moves the unit to the normal

stop state.

(Operation)
• Press the ZONE1,2

button.

• Set the operation to the heating mode.
• After a while, forced defrosting signals are transmitted to the outdoor unit, and the unit starts defrosting.

(Forced defrosting lasts for up to 10 minutes.)

• After the defrosting, the heating operation starts.
• To perform defrosting again, start with

1

above.

(Performing the forced defrosting once cancels the forced defrosting setting above described.)

13. Rated Operation Setting

The FC code setting (See 2-2) can activate the rated operation mode during a heating operation.

(Preparation)

1

Press the remote controller buttons TEST

, SET

,

and SELECT

, at the same time for 4 seconds

or longer.(Make sure that no operation is in progress.)

2

Specify CODE NO. (FC) 91 with the TEMP.

button for temperature setting.

3

Set DATA to 0001 with the TIME

button for timer

setting. (See display

)

(Factory setting is 0000)

4

Press the SET

button. (If OK

lights, the status is

confirmed)

5

Pressing the TEST

button moves the unit to the normal

stop state.

(Operation)
• Press the ZONE1,2

button.

• Set the operation to the heating mode.
• After a while the outdoor unit starts an operation with the rated operation frequency.

3 horsepowers: HWS-802XWH**-E/HWS-802H-E 66.0Hz
4 horsepowers: HWS-1402XWH**-E/HWS-1102H-E 44.4Hz
5 horsepowers: HWS-1402XWH**-E/HWS-1402H-E 56.4Hz

2

3

4

1

5

2

3

4

1

5

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 117 Monday, October 5, 2009 2:09 PM

Advertising