8-2.

Operation
Mode and
Control Method

11) AUTO operation
An auto operation sets the water temperature TSC_F depending on the outside temperature TO by following the table
below.

1) How to operate

• Pressing the remote controller [ZONE1, 2] button and then the [AUTO] button starts AUTO operation for heating. An

operation starts at the set temperature of straight -line approximation for the following: water temperature 40°C with
the outside temperature -20°C (FC), 35°C with -10 °C (T1)(FC), 30°C with 0°C (FC), 25°C with 10°C (T3), and 20°C
with 20°C (TC).

• For 2-temperature control, although Auto-Curve in ZONE2 shows 80% of that of ZONE1 (FC), the water temperature

setting does not fall below 20°C.

• During an AUTO operation, pressing again the [AUTO] button returns to the usual manual set heating operation.
• The remote controller displays "A" as the temperature during an AUTO operation.

(When 2-temperature control is enabled, the remote controller displays "A" "A".)

• Long-pressing the [AUTO] button during an AUTO operation activates the Auto-Curve FC change mode, enabling

the set Auto-Curve water temperature to be changed in the ±5K range. (FC_27)

• Even if the temperature setting is changed during an AUTO operation, the operation continues.
• An AUTO operation works with a heating operation only, not with a cooling or a hot water supply operation.

Related FC

Item

Operation flow and applicable data, etc.

-10

(T1)

-20

20(E)

25(D)

30(C)

35(B)

40(A)

0

10

(T3)

20

Auto-Curve
ZONE1

Auto-Curve
ZONE2

FC No.

Setting item

Default

Setting available range

27

Set temperature shift with heating set to Auto

0

-5 to 5 k

29

Outside air temperature T1 temperature

-10°C

-15-0°C

2B

Outside air temperature T3 temperature

10°C

0-15°C

2C

Set temperature when out side air temperature is -20 °C.

40°C

20-55°C

2D

Set temperature when out side air temperature is -10 °C (T1).

35°C

20-55°C

2E

Set temperature when out side air temperature is 0 °C.

30°C

20-55°C

2F

Set temperature when out side air temperature is 10 °C (T3).

25°C

20-55°C

30

Set temperature when out side air temperature is 20 °C.

20°C

20-55°C

31

Auto-Curve ratio of
ZONE2

80%

0-100%

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 46 Monday, October 5, 2009 2:09 PM