143

Toshiba

6

Compressor
Compressor lead

2. Attach the compressor

1) Attach the compressor in the reverse order of the

removal.

Note)

• Be sure to replace the compressor lead after the

compressor replacement. (Compressor lead
spare parts code: 43160591)
At this time, wind the ferrite core with the
compressor lead for 4 times.
Bind the compressor lead that is long with a
commercially available binding tie. When doing
this, be careful for the compressor lead not to
contact the discharge pipe.

• Fix the removed sensors and pulse motor valve

coil lead to the outlet and suction pipes through
the piping cover by using a binding tie. At this
time, be careful for the sensors and pulse motor
valve coil lead not to contact the discharge pipe.
(To fix the sensors and leads, use the black
piping cover for heat resistance and a
commercially available binding tie for heat
resistance.)

• Attach the soundproofing board (Inward

winding, Outward winding), as shown in the right
figure, through between the compressor and
between the piping and parting board.

• Place the compressor lead and the compressor

case thermostat so that they fall into between
the inward winding and outward winding of the
soundproofing board.

No.

Exchange parts

name

Work procedure

Remarks

Black piping cover for heat resistance,
and Binding tie for heat resistance
Sensors (TL, TO, TE, TD, TS)
Pulse motor valve coil lead

Piping cover, Binding tie
Sensors (TL, TO, TE, TS)
Pulse motor valve coil lead

Keep sensors away
for not contacting outlet pipe

Pulse motor valve coil lead

Suction pipe

Piping cover, Binding tie, TS sensor

Outlet pipe

Place soundproofing board (Outward winding)
through between suction pipe and accumulator

Compressor
lead

Ferrite core

Suction pipe

Accumulator

Soundproofing
board (Upper)

Soundproofing board
(Outward winding)

Do not make gap between soundproofing
boards (Upper and Outward winding)

Header pipe

Overlap soundproofing
board (Outward winding)
at this position

Place soundproofing
board (Inward winding)
through between suction
pipe and header pipe

0 to 50
(Compressor lead
positioning standard)

Bind the lead at 2 positions
with a commercially
available binding tie

Wind ferrite core with
compressor lead for 4 times.

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 143 Monday, October 5, 2009 2:09 PM