8-2.

Operation
Mode and
Control Method

2) Heating operation
<Operation only for ZONE1>
• This operation is enabled when DP_SW12_2 ZONE1 is set to "ON" (default).
• The remote controller displays

settings, and only the set temperature of

can be changed.

<Operation for ZONE1 and ZONE2 (2 temperatures control)>
• This operation is enabled when DP_SW12_2 ZONE1 is set to "ON" (default) and DP_SW12_3 ZONE2 to "ON".
• The remote controller displays

settings, and the set temperatures of

can be changed.

• To set temperatures for

and

, use SELECT

to switch

and

.

• For 2 temperatures control, the flow adjustment of MIXING VALVE controls the water temperature of

. For

details,
see the description on MIXING VALVE control in 8-3-5.

1) Operation start condition

Pressing the [ZONE1, 2] button of remote controller starts a
heating operation. *1 *2

2) Operation mode selection

An operation mode is determined according to the temperature
of TWI sensor.
• Heat pump operation selection *1 *2

When TWI < TSC_F (d zone in the right figure) is met, the heat
pump operation is selected.

• Thermostat status "OFF"

When TWI TSC_F (e zone in the right figure) is met, the
thermostat status "OFF" is selected.

3) Operation stop condition

When the following condition is met, the heating operation stops.
• The remote controller gives a stop instruction.

*1: When the outside temperature is -20°C or below, the heater

operation is selected even if the TTW temperature falls into "d
zone".

*2: When "Hot water supply" and "Heating" are simultaneously in

operation, the heater operation may be selected depending on
the outside air temperature.

Related FC

Item

Operation flow and applicable data, etc.

TWI

TSC_F

C_f = 0

Thermostat off
operation

e zone

d zone

diff2K

Heat pump operation

TSC_F is a heating temperature

set with remote controller

FC No.

Setting item

Default

Setting available range

1A

Upper limit of heating (Zone1) limited temperature

55

37-55°C

1B

Lower limit of heating (Zone1) limited temperature

20

20-37°C

1C

Upper limit of heating (Zone2) limited temperature

55

37-55°C

1D

Lower limit of heating (Zone2) limited temperature

20

20-37°C

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 40 Monday, October 5, 2009 2:09 PM