Toshiba HWS-802XWHT6-E User Manual

Page 116

Advertising
background image

115

Toshiba

9. Anti Bacteria Setting

This setting regularly raises the hot water cylinder temperature to prevent bacteria from growing.

1

Press the HOT WATER

button to start a hot water

supply operation.

(Normal hot water supply operation)
(No anti bacteria setting is provided to heating and cooling.)

2

Pressing the ANTI BACTERIA

button displays the

symbol. (See display

)

(The set temperature does not change) The hot water supply operation
of 75°C starts.
The anti bacteria operation raises water temperature to 75°C with the
heat pump and heater, and automatically ends after 30 minutes.

3

After that, an anti bacteria operation automatically starts at the
set time and cycle.

4

Pressing the ANTI BACTERIA

button makes

disappear, and the anti bacteria operation does not start.

<How to set anti bacteria temperature and holding time>

In FC_0A or 0B (See 2-2), the set temperature and holding time can be changed.
FC_0A: Set temperature change range 70 to 80°C (75°C: default)
FC_0B: Holding time change range 0 to 60 minutes (30 minutes: default)

<How to set anti bacteria start time and cycle>

1

Press the ANTI BACTERIA

button for 4 seconds

or longer. (See display

)

(Moves to the anti bacteria time setting mode)
"0C" in the Code No. field and the currently set

and

indication blink.

2

Press the TIME

button to set a desired start time.

Pressing SET

changes DATE (set time) 0C, and

indication to be lit and the setting is confirmed.

3

Press the TEMP.

button to change Code No.

to "0d".

The "0d" and

indication blink.

4

Press the TIME

button to set a desired cycle.

Pressing SET

changes DATE (set time) 0d, and

indication to be lit and the setting is confirmed.

5

Press the TEST

button to exit the anti bacteria time setting mode.

2,4 1

2,
4

3

5

1

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 115 Monday, October 5, 2009 2:09 PM