8-3.

Hydro Unit
Control

2) Control at the time of heating heater operation

• Controlled Object: Backup heater, Booster heater

The backup heater control starts when 13 minutes has passed after the heating heat pump operation started.
The backup heater control increases, decreases, or maintains the number of heaters every 10 minutes (FC)
depending on the difference between the heating set temperature (TSC_F) and the heater outlet temperature
(THO). Note that when the heating set temperature (TSC_F) is reached, the unit stops energizing the heater.

The single-phase model of 3 kW has the backup heater 1 only.
The three-phase model of 6 kW has heater 1+2 of 6 kW.
Contact point output only is available for booster heater.

Related FC

2-3) Heater control at the time of defrosting

• Object to be controlled: Backup heater
When a defrosting operation starts during the heating heat
pump operation, the unit energizes a backup heater (3 kW)
according to the heater outlet temperature sensor (THO) and
the set temperature (TSC_F) as follows.

1) When the heater outlet temperature sensor (THO) drops to

the temperature of 2°C below the set temperature

Defrosting ends according to the usual heater control.

2-4) Forcible heater energization

To prevent freeze, the unit energizes or stops energizing a backup heater (3 kW) regardless of the unit status, not
operated or in operation.
• Object to be controlled: Backup heater
1) Energization start condition: TWO < 4 or TWI < 4 or THO < 4
2) Energization stop condition: TWO 5 and TWI 5 and THO 5
Defrosting ends according to the usual heater control.

2-5) No heater operation

According to the DP_SW11 setting, the unit switches the energize/ not energize for the hot water cylinder, backup
heater, and booster. For details, see 10-1.

Item

Operation flow and applicable data, etc.

70

TSC_F-2

TSC_F-4

TSC_F-0

THO

E zone

D zone

C zone

B zone

A zone

Diff : 2K

Diff : 2K

Diff : 2K

Abnormality detection

Heater off

KEEP

Heater output down every
5, 10, 15, or 20 minutes

Heater output up every
10, 20, 30, or 40 minutes

Status

Heater ON / OFF

Heater 1

Backup heater 3 kW = ON

Heater 2

Backup heater 9 kW = ON

Heater 3

Heater 2 + Booster heater

FC No.

Setting item

Default

Setting available range

20

Hot water supply heat pump start temperature

38°C

20-45°C

21

Hot water supply heat pump stop temperature

45°C

40-50°C

33

Heater control of down time

1:10 mins

0:5 mins 2:15 mins 3:20 mins

34

Heater control of up time

0:10 mins

1:20 mins 2:30 mins 3: 40 mins

Heater off

Heater 1

Heater 1

TSC_F

TSC_F-

β (β=2)

TSC_F-

α (α=4)

THO

Status

Heater ON / OFF

Heater 1

Backup heater 3 kW = ON