8-4.

Outdoor unit
control

6) Defrosting control
This control defrosts the outdoor heat exchanger. The temperature sensor (TE sensor) of the outdoor heat exchanger
determines frost formation, and then defrosting is performed in the 4-way valve reverse defrosting method.

1) During a heating operation, defrosting is performed when the TE sensor meets any of the conditions in A through D

zones.

2) During defrosting, when TE sensor maintains 12°C or higher for 3 seconds or 7°C TE < 12°C for a minute, the

defrosting ends. Also, when defrosting continues for 10 minutes even if the TE sensor temperature is below 7°C, the
defrosting ends.

3) After the defrosting, stop the compressor for approx. 40 seconds before starting a heating operation.
4) Switching the jumper "J805" and "J806" of the outdoor control board can change the time of d above mentioned.

(Factory setting: 150 minutes)

Jumper switching

O: Short circuit ×: Open

Item

Operation flow and applicable data, etc.

Heating operation starts

-2

-5

-10

-23

(-25)*

2

TE
[

°C

]

0

10

15

39

45

55

d

[min]

D zone

A zone

B zone

C zone

*

1

*

1

In 10 to 15 minutes after the heating

operation starts, the lowest value of
TE is recorded as TEO, and the
lowest temperature of To as ToO.

*

2

Inside brackets: For 802H-E

To Normal

A Zone

Maintain " (TEO - TE) - (ToO - To) 3°C" for 20 secs

B Zone

Maintain " (TEO - TE) - (ToO - To) 2°C" for 20 secs

C Zone

Maintain " TE -23°C" for 20 secs (1102, 1402H-E)

Maintain " TE < -25°C" for 20 secs (802H-E)

D Zone

Accumulate compressor operation status of TE < -2°C for 150 mins

To Normal

A Zone

Maintain " TEO - TE 3°C" for 20 secs

B Zone

Maintain " TEO - TE 2°C" for 20 secs

C Zone

Maintain " TE -23°C" for 20 secs (1102, 1402H-E)

Maintain " TE < -25°C" for 20 secs (802H-E)

D Zone

Accumulate compressor operation status of TE < -2°C for 150 mins

J805

J806

d (1102,1402H-E)

d (802H-E)

O

O

150 mins (Factory setting)

150 mins (Factory setting)

O

×

90 mins

90 mins

×

O

60 mins

60 mins

Ч

Ч

30 mins

30 mins

ON

OFF

ON

OFF

ON

OFF

500pulse
200pulse

0pulse

0s

30s

40s

Defrosting operation

0s

30s

10s

40s

Outdoor PMV

4-way valve

Outdoor fan

Compressor