Toshiba HWS-802XWHT6-E User Manual

Page 145

Advertising
background image

144

Toshiba

6

Compressor
Compressor lead

3. Vacuuming

1) Connect the vacuum pump to the charge port of

the gas piping valve to operate the vacuum pump.

2) Perform vacuuming until the vacuum low pressure

gauge shows 1(mmHg).

Note)

Open fully the pulse motor valve before
vacuuming. With the valve closed, vacuuming
between the outdoor unit liquid valve and the pulse
motor valve may fail.

How to make pulse motor valve forcible full open
• Turn on the electric leakage breaker.
• Set the SW804 dip switch 1 and 3 on the outdoor

unit control board to ON.

• Press SW801 on the outdoor unit control board

for 1 second or longer.

• After pressing SW801 for 1 second or longer,

turn off the electric leakage beaker within 2
minutes.

4. Charge refrigerant

1) Add refrigerant whose amount is defined

according to the piping length from the valve
charge port. (HWS-802H : 1.8kg)

7

Pulse motor valve coil

1. How to remove

1) Perform the step 1-1 and step 3.
2) Remove the coil from the pulse motor valve body

while pulling the coil upward to release the spring
holding the copper pipe.

2. How to attach

1) Fix the spring to the copper pipe.

No.

Exchange parts

name

Work procedure

Remarks

SW801

SW804

Pulse motor
valve body

Pulse motor valve coil

Spring

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 144 Monday, October 5, 2009 2:09 PM

Advertising