Toshiba HWS-802XWHT6-E User Manual

Page 45

Advertising
background image

44

Toshiba

8-2.

Operation
Mode and
Control Method

8) Anti bacteria (ANTI BACTERIA) operation
An anti bacteria operation regularly performs a Hot water supply operation with the set temperature TSC_H = 75°C (can
be set with FC_0A).

1) How to operate

• Pressing the [HOT WATER] button and then the remote controller [ANTI BACTERIA] button changes the setting to

TSC_H = 75°C at the set cycle and time (both can be set with the remote controller FC) to start ANTI BACTERIA
operation.

• The first auti bacteria operation starts when press the [ANTI BACTERIA] button and starting time come.
• When the set temperature 75°C is reached after the ANTI BACTERIA operation started, the set temperature remains

another 30 minutes (can be set with FC_0B).

• The priority zone determined by the outside temperature selects an operation, Hot water heat pump or hot water

supply heater.

• The hot water heat pump operation, when selected, ignores the hot water supply start condition (TTW < 38°C) and

forcibly performs a hot water operation.

• During ANTI BACTERIA operation (Forcible hot water operation at 75°C), the hot water set temperature display is

not changed. If it is changed from the remote controller, the normal hot water set temperature will be changed.

Related FC

Item

Operation flow and applicable data, etc.

ANTI BACTERIA button set to "ON"

Anti bacteria start time

75°C hot water supply operation

75°C hot water supply operation for 30 minutes

Usual hot water supply operation

(Set temperature: 40°C to 75°C)

HOT WATER button set to "ON"

Caution

• During a 75°C hot water supply operation with ANTI

BACTERIA, the remote controller does not display 75°C.

• Be careful not to burn yourself; Output water may be hotter

than that displayed on the remote controller.

FC No.

Setting item

Default

Setting available range

0A

Anti bacteria set temperature

75°C

70-80°C

0B

Anti bacteria holding time

30 mins

0 - 60 mins

Remote control

OC

Anti bacteria start time

22:00

0:00-22:00

Remote control

OD

Anti bacteria operation cycle

7 days

Every day to 10 days

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 44 Monday, October 5, 2009 2:09 PM