Toshiba HWS-802XWHT6-E User Manual

Page 69

Advertising
background image

68

Toshiba

A07

Pressure switch operation

The pressure switch operates for 300

sec continuously during the heat pump

operation.

O

×

1. Almost no or little water flow.

2. Defect of the flow switch.

3. On-load operation under the above

conditions.

4. Defect in the pressure switch.

1

79

A08

Low pressure sensor operation error

The low pressure sensor detected 0.2

MPa or less.

O

×

1. Almost no or little water flow.

2. Defect of the flow switch.

3. On-load cooling or prolonged

defrosting (a lot of frost formation)
under the above conditions.

8

80

4. Defect in the low pressure sensor.

2

A09

Overheat protection operation

When the thermostat of the backup

heater activates during the operation of

the heat pump or backup heater.

When the thermostat operation is

activated while it has been stopped.

O

×

1. No water (heating without water) or

no water flow.

2. Defect of the flow switch.

2

81

3. Defect of the backup heater (poor

automatic reset thermostat).

1

A11

Operation of the release protection

When the TWO release counts to 10.

Heating
Cooling

×

Hot water

O

×

1. Almost no water flow.

2. Defect of the flow switch.

3. Check the water outlet temperature

sensor (TWO).

10

82

A12

Heating, hot water heater

The antifreeze control is detected under

the condition of TWI<20°C while

TWI

>

15°C, TTW>20°C is not detected

after the heater backup.

O

O

1. Activated by a large load of heating

or hot water supply.

2. Check the heater power circuit

(backup or hot water cylinder
heater).

• Power supply voltage, breaker,

power supply connection

1

83

E03

Regular communication error

between hydro unit and remote

controller

When there is no regular communication

from the remote control for 3 min, or

when no remote control is equipped.

×

O

1. Check remote control connection.

2. Defect in the remote control.

1

E04

Regular communication error

between hydro unit and outdoor unit

The serial signal cannot be received

from outdoor.

O

O

1. Check the serial circuit.
• Miswiring of the crossover between

the water heat exchanger and the
outdoor unit

1

84

F03

TC sensor error

Open or short circuit in the heat

exchange temperature sensor.

O

O

1. Check the resistance value and

connection of the heat exchange
temperature sensor (TC).

1

85

F10

TWI sensor error

Open or short circuit in the water inlet

temperature sensor.

O

O

1. Check the resistance value and

connection of the water inlet
temperature sensor (TWI).

1

86

F11

TWO sensor error

Open or short circuit in the water outlet

temperature sensor.

×

O

1. Check the resistance value and

connection of the water outlet
temperature sensor (TWO).

1

87

F14

TTW sensor error

Open or short circuit in the hot water

cylinder sensor.

×

O

1. Check the resistance value and

connection of the hot water cylinder
sensor (TTW).

1

87

Check

code

Diagnostic functional operation

Determination and action

Number of

abnormalities

for

confirmation

Detailed

item

Operational cause

Backup
present

Automat

ic reset

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 68 Monday, October 5, 2009 2:09 PM