Toshiba HWS-802XWHT6-E User Manual

Page 77

Advertising
background image

76

Toshiba

[A03] Error Temperature rise and error short circuit

Replace TTW sensor

No

(TTW 85°C is detected)

TTW sensor

characteristic is correct

Yes

No

Hot water cylinder heater

is energized

Yes

No

At normal

temperature, tank thermostat

is energized

Yes

Replace hot water
cylinder thermostat

No

Hot water cylinder

thermostat operates

Yes

Operation
temperature 82°C

Start

Replace water heat exchange control board

Replace Mg-sw

No

Mg-sw (RY05) for

heater operates

Yes

Operating noise at normal time

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 76 Monday, October 5, 2009 2:09 PM