9-4. Diagnosis flow chart for each error code

9-4-1. Hydro unit failure detection

[A01] Error Pump flow determination

Pump rotates

Replace TC sensor

Remove waste

Dirt clogging inside
water circuit

12 M or longer water
pipe to a branch,
or 5 or less branches

Fit buffer tank and the
second pump

Attach or replace
flow switch

Connect flow switch
connector to board

No

No

(Identify causes, and resolve)

(strainer)

Excess air noise

comes from inside

the pump

Flow switch is

connected to board

Built-in pump is

connected to board

Flow switch is normal

Chattering noise comes

from flow switch

Pump stops 2-3

minutes after its rotation

started

TC sensor characteristic

is correct

Yes

Yes

[A01] occurs

Operation restarts

Water heat exchanger control board

is defective, replace it

Perform

air vent

Flow shortage

No (No pump sound)

No

Connect pump
connector to board

No

Replace flow switch

No

No

No

No

Yes

Flow switch is normal

Yes

Replace pump

Yes

Yes

No

Yes

Yes