Toshiba HWS-802XWHT6-E User Manual

Page 46

Advertising
background image

45

Toshiba

8-2.

Operation
Mode and
Control Method

9) Night set back (NIGHT SET BACK) operation
A night set back operation performs heating at 5°K lower and cooling at 5°K temperatures against the remote controller
set temperature from the setting start time (22:00) to the end time (6:00) every day.

Note) • Set the remote controller time before starting a NIGHT SET BACK operation.

• The set time can be changed with remote controller FC.

Related FC

10) FROST PROTECTION operation
A frost protection operation performs heating at the set temperature RSC_F = 15°C (FC).

1) How to operate

• Pressing the remote controller [ZONE1, 2] button and then the [FROST PROTECTION] button starts a heating

operation at the set temperature of 15°C.

• Pressing again the [FROST PROTECTION] button cancels the FROST PROTECTION operation.
• The remote controller displays "F" as the temperature during FROST PROTECTION.
• A set temperature change during a FROST PROTECTION operation cancels the operation.

Related FC

Item

Operation flow and applicable data, etc.

FC No.

Setting item

Default

Setting available range

Remote controller

OE

Night set back start Time setting

22:00

0:00-23:00

Remote controller

OF

Night set back end Time setting

6:00

0:00-23:00

26

Night set back setting Temperature width

5 deg

3 -20 deg

FC No.

Setting item

Default

Setting available range

3A

FROST PROTECTION Yes / No

1: Yes

0: No

3B

FROST PROTECTION Set temperature

15°C

10-20°C

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 45 Monday, October 5, 2009 2:09 PM