8-4.

Outdoor unit
control

10) High temperature release control

1) To prevent excessive hi pressure rise, operation frequency is controlled by the TL sensor when cooling and by TWO

sensor when heating.

2) If the TL sensor when cooling or the TWO sensor when heating detects an abnormal stop zone temperature, the

compressor stops and the abnormality detection counter increments.

3) When the compressor stops in 2), the operation restarts when the temperature returns to the usual operation zone

("e" or below) after 150 seconds.

4) When the compressor stops in 2), the abnormality detection counter is cleared when the operation continues for 10

minutes. If the counter counts 10 times, error code is displayed and the compressor does not restart.

5) For details about an check code displayed, see the check code list.

Item

Operation flow and applicable data, etc.

[°C]

Heating TC
Cooling TL

a

b

c

d

e

Abnormal stop

Frequency normal down

Frequency slow down

Frequency hold

Frequency slow up

(up to the point instructed)

As instructed

802H-E

1102H-E, 1402H-E

Heating

Cooling

Heating

Cooling

TC (TWO+2)

TL

TC (TWO+2)

TL

a

61°C

63°C

62°C

63°C

b

56°C

62°C

57°C

62°C

c

54°C

60°C

55°C

60°C

d

52°C

58°C

53°C

58°C

e

48°C

54°C

49°C

54°C

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 63 Monday, October 5, 2009 2:09 PM