3. tools, 3-1. necessary tools, General tools (conventional tools are available) – Toshiba HWS-802XWHT6-E User Manual

Page 11

Advertising
background image

10

Toshiba

2-3. Tools

2-3-1. Necessary tools

In Air to Water Heat Pump using R410A, the service port diameter of packed valve of the outdoor unit is changed
to prevent mixing of other refrigerant. To reinforce the pressure resistance, flare dimensions and opposite side
dimensions of flare nut (For Ø 12.7 copper pipe) of the refrigerant piping are lengthened.
Because the refrigerating machine oil is changed, mixing of oil may generate sludge, clog capillary, or cause other
problems. Accordingly, the tools to be used include:
• tools dedicated for R410A (Those that cannot be used for the conventional refrigerant, R22)
• tools dedicated for R410A, but can be also used for the conventional refrigerant, R22
• tools that can be used for the conventional refrigerant, R22.

The following table shows the tools dedicated for R410A and their interchangeability.

Tools dedicated for R410A (The following tools must be for R410A)

Tools whose specifications are changed for R410A and their interchangeability

* (Note 1) Flaring for R410A by using the conventional flare tool requires projection margin adjustment. This

adjustment requires copper pipe gauge or other instrument.

* (Note 2) A charging cylinder for R410A is currently under development.

General tools (Conventional tools are available)

In addition to the above dedicated tools, the following equipment also available for R22 is necessary as the general
tools.

Also prepare the following equipment for other work methods or run check.

No.

Tool to be used

Usage

R410A Air to Water Hear Pump

installation

Conventional refrigerant

Air to Water Heat Pump

installation

For R410A

Existence of new

equipment

Conventional

equipment can be

used

New equipment can be

used with conventional

refrigerant

1

Flare tool

Pipe flaring

Yes

*(Note 1)

Yes

2

Copper pipe gauge for

adjusting projection margin

Flaring by conventional

flare tool

Yes

*(Note 1)

*(Note 1)

3

Torque wrench (For Ø15.9)

Connection of flare nut

Yes

No

No

4

Gauge manifold

Evacuating, refrigerant
charge, run check, etc.

Yes

No

No

5

Charge hose

6

Vacuum pump adapter

Vacuum evacuating

Yes

No

Yes

7

Electrical balance for

refrigerant charging

Refrigerant charge

Yes

No

Yes

8

Refrigerant cylinder

Refrigerant charge

Yes

No

No

9

Leakage detector

Gas leakage check

Yes

No

Yes

10

Charging cylinder

Refrigerant charge

*(Note 2)

No

No

1. Vacuum pump

Use this by attaching vacuum pump

adapter.

4. Reamer

9. Hole core drill (Ø65)

5. Pipe bender

10. Hexagon wrench

(Opposite side 4mm)

6. Level vial

2. Torque wrench (For Ø6.35)

7. Screwdriver (+, –)

11. Tape measure

3. Pipe cutter

8. Spanner or Monkey wrench

12. Metal saw

1. Clamp meter

3. Insulation resistance meter

2. Thermometer

4. Electroscope

+00A09-002_01EN_SVM_ALL_Air_to_Water.book Page 10 Monday, October 5, 2009 2:09 PM

Advertising