4-2. outdoor unit failure detection, Diagnosis procedure for each check code – Toshiba HWS-802XWHT6-E User Manual

Page 92

Advertising
background image

91

Toshiba

9-4-2. Outdoor Unit Failure Detection

Diagnosis procedure for each check code

• One check code may indicate multiple symptoms. In such a case, see the LED indication on the outdoor board

to narrow down the check details.

• The handy remote controller displays a check code only when the same failure repeatedly occurs while the LED

on the outdoor board indicates an error even if it occurs only once. This may cause indication inconsistency
between the remote controller and LED.

Outdoor board LED indication method

Dip switch setting

• Setting 1 only of SW803 to ON indicates the latest failure.

Because the error history is recorded, you can see the detail
even after the power is once turned off. (Not including outside
air temperature sensor (TO) failure)

• After check work is done or when outside air temperature

sensor (TO) failure is detected, set all the SW803 switches to
OFF.
(An abnormality now is indicated.)

Indication switching

• One or more LEDs of D800 through D804 lit yellow indicates

that a failure occurred. <Indication 1>

• With the status above, pressing the SW800 button for one

second causes the yellow LED to blink. <Indication 2>

• Pressing again SW800 for one second or longer returns to

<Indication 1>.

• The combination of <Indication 1> and <Indication 2> can

determine what kind of abnormality.

Check code

Outdoor LED

indication

Check and Action procedure

(No specific description indicates outdoor unit parts.)

[H01]

<Indication 1> <Indication 2>

[Compressor fails]

1

ON

234

<Latest abnormality>

SW803 1 only is ON

1

ON

234

<Abnormality now>

SW803 All OFF (Initial status)

D800 (yellow)
D801 (yellow)
D802 (yellow)
D803 (yellow)
D804 (yellow)
D805 (green)

Off Light Blink

(Normal) (Abnormality occurs)(Press SW800)

(Example of outlet temperature sensor failure)

<Indication 1> <Indication 2>

Power voltage is normal.
230ACV ± 23V

Improve power line

Check outdoor control board

If defective, replace it

No

Yes

Abnormally over loaded

Deal with or remove causes

Yes

No

Wiring connection is normal.
Compressor lead (Board side, compressor
side reactor lead, power lead)

Check and correct wiring
connection

No

Yes